Viscosity-compensated flow monitor with flow meter, up to 300 bar
{{ bild.Beschreibung }}
{{ bildGross.Beschreibung }}
{{ bildGross.Beschreibung }}
{{ bildGross.Beschreibung }}
Application:
Flow monitors monitor a flow quantity that can be set. If this is exceeded or undershot, a contact gets actuated. A voltage supply is not necessary because of the potential-free reed contacts. The additional scale allows reading the momentary flow directly on the instrument.
Temperature range:
-20 to +120 °C, Environment: max. +80 °C
Protection class:
IP 53
Measurement principle:
Spring loaded float
Installation position:
arbitrarily (preferred from bottom to top)
Direction of flow:
only in one direction
Electrical connection:
Right-angle connector installation size 3, 3-pole (DIN 43650 / EN 175301-803 A) (Flat pin)
Switch type:
Closer (NO)
Switching capacity:
250 V AC, 100 VA, max. 5 A / 250 V DC, 100 W, max. 5 A
Media:
Oils and other fluids with 30 - 600 cSt viscosity (0.1 - 0.8 l/min: max. 400 cSt)
Advantages:
•Scale and switching point do not have to be adjusted according to the medium and pressure.